Description
Description |
---|
T11040M2 – 4 Zones Conventional Fire Detection Alarm System Panel Sigma CP T11 Kentec |
The Sigma CP range comprises a series of conventional fire detection alarm system panels designed in compliance with European standards BS EN54-2 and BS EN54-4 for Fire Detection and Fire Alarm systems – Control and Indicating Equipment. |
The range includes 2, 4, and 8 zone fire detection alarm system panels. The Sigma T11 range employs a two-wire system, where detectors, call points, and sounders are wired to the same pair of cables, eliminating the need for separate sounder circuit cables and providing the flexibility of zoned or two-stage sounder operation. |
Notes: For 2-wire T series panels, compatible detectors and call points must be used. All sounders must be polarized. |
All fire detection alarm system panels feature an integral, mains-powered battery charger and power supply designed according to the requirements of BS EN54-4. |
Features & Benefits |
---|
– Fully certified to BS EN54-2 and BS EN54-4 |
– 2-wire Versions available in 2, 4, or 8 zones |
– Compatible for use on BS5839: Part 1: 2002 installations |
– 2-wire repeaters and ancillary boards |
– Fully programmable using simple menu options |
– Adjustable sounder delay time |
– Sounder configuration options |
– Zonal sounder delay for detectors only |
– Zonal sounder delay for call points only |
– Coincidence input selection |
– I.S Barrier selection by zone |
– Short circuit fire detection by zone |
– Non-latching zones |
– Silent zones |
– Zone input delay |
– General panel configuration |
– Simple, single board construction |
– Installer-friendly |
– Compatible with a wide range of fire detection devices |
– 3 Amp power supply |
– Auxiliary power output |
Technical Specifications |
---|
Construction: 1.2 mm mild sheet steel |
Finish: Epoxy powder-coated |
Colour – lid & box: BS 00 A 05 grey – fine texture |
Colour – control plate & labels: RAL 7047 light grey – satin |
Supply voltage: 230 VAC (+10%/-15%) |
Mains supply fuse: 1.6 A 250V |
Power supply DC rating: 24V 3A |
Maximum battery size: 7Ah 12V (2 per panel) |
Fault contact rating: 30 VDC 1A |
Local fire contact rating: 30 VDC 1A |
Fire contact rating: 30 VDC 1A |
Sounder output rating: 0.5A per output (Max 1.6A over all outputs) |
Detection zone current: 1.6 mA |
Detection zone EOL resistor: 6K8 5% |
Active EOL: K14606K (optional) |
Sounder output EOL resistor: 10K 5% |
Cable capacity: 2.5 mm² |
Operating temperature: -5°C to +50°C |
Operating humidity: < 95% (non-condensing) |
Dimension: 385 mm x 310 mm x 90 mm |
Standby current 2 zones: 0.065 A |
Standby current 4 zones: 0.075 A |
Standby current 8 zones: 0.093 A |
Alarm current 2 zones: 0.15 A |
Alarm current 4 zones: 0.30 A |
Alarm current 8 zones: 0.63 A |